HZJF-124 digital partial discharge detector is the newly development digital partial discharge testing machine. It adopts 32 bits high performance singlechip circuit, combining touching-screen operation, improve the service life of the instrument. The instrument can be automatically corrected by one button, detecting sensitively, wide dynamic amplifier system, anti-interference strongly.
Main Technique Parameters:
1. The equivalent capacity range of test object: 6pF-250μF
2. Measurement Range: 0.1pC-10000nC
3. Channel Number: Single channel
4. Detecting sensitivity and permitted current(Refer below form)
Input unit No. |
Tuning Capacity Range |
Sensitivity(pC)(Imbalanced Circuit) |
Permitted Effective Current Value |
Imbalanced Circuit |
Balanced Circuit |
1 |
0-25-100pF |
0.02 |
30mA |
0.25A |
2 |
25-100-400pF |
0.04 |
50mA |
0.5A |
3 |
100-400-1500pF |
0.06 |
120mA |
1A |
4 |
400-1500-6000pF |
0.1 |
0.25A |
2A |
5 |
1500-6000-25000pF |
0.2 |
0.5A |
4A |
6 |
0.006-0.025-0.1μF |
0.3 |
1A |
8A |
7 |
0.025-0.1-0.4μF |
0.5 |
2A |
15A |
8 |
0.1-0.4-1.5μF |
1 |
4A |
30A |
9 |
0.4-1.5-6.0μF |
1.5 |
8A |
60A |
10 |
1.5-6.0-25μF |
2.5 |
15A |
120A |
11 |
6.0-25-60μF |
5 |
25A |
200A |
12 |
25-60-250μF |
10 |
50A |
300A |
7R |
Resistance |
0.5 |
2A |
15A |
5. Ellipse Scanning Time Basement
(1)Frequency: 50Hz, 60Hz, 100Hz, 150Hz, 200Hz, 400Hz
(2)Rotation: 30 degree per gear, 120 degree ratational
(3)Working way: Ellipse-sine wave- straight line
6. Display Unit
10.1 inches capacitive type touching screen.
7. Amplifier
(1) 3dB low frequency end frequency FL 10, 20, 40kHz to choose
(2) 3dB high frequency end FH 80, 200, 300kHz to choose
(3) Gain adjust, coarse tuning 6 gears, the gain gap between gears 20±1dB, fine tuning range >20dB
(4) Positive and negative pulse response asymmetry <1dB
8.Time window
Window width: adjustable, 5°~170° under 50Hz
Window location: each window can rotate 0°~170°
The two time window can be opened separately or simultaneously
9. Pulse Crest
Touching screen display, display 1 decimal place(≥10pC), display 2 decimal place(<10pC), error:±3%(Measured at full scale)
10. Testing Voltage Display
(1) Measurement range: 150kV
(2) Input impedance: >1mΩ
(3) Display: Touching display, reach to 1 decimal place
(4) Error: ±1%
11. Testing Frequency Display
Error: Less than ±1%
12. Zero-lable System
Zero lable, consistent with all ellipse scanning frequency
13. Structure
(1) Sizes: 370mm(Width), 460mm(Depth), 215mm(Height)
(2) Weight: About 12.5kg
Company Profile
Kiyu Power
is a high-tech enterprise professionally engaged in R & D, manufacture and marketing of power testing products, instruments, power industry automation systems for 20 years.We export completed set to Korea, Singapore, Vietnam, India, Ecuador, Paraguay, Pakistan, Philippines, Russia, Italy, Austria, Portugal, Chile such as PD test system, impulse voltage generator, temperature rising test system, transformer comprehensive test system, cable fault detect system and varies of instruments for transformer, circuit breaker, switchgear, lightning arrestor, insulator, cable, battery, SF6 gas and so on.