Remark: English version is available for all of the testing equipment.
CYJC series insulated oil dielectric strength tester can be divided into single cup three cups and multi-cups.The instrument is simple and easy to operate due to adopt automatic digital microcomputer control, the measurement precision is high, anti-interference ability is strong, safe and reliable.
Main Technical Parameters
1.Booster Capacity: 1.5kVA
2.Step-up Speed: 2.0 kV/s, 2.5kV/s, 3.0 kV/s, 3.5kV/s, 4 gears option, error 0.2kV/s
3.Output Voltage: 0~80 kV(Voltage accuracy: ±2% reading+ 2 dgt)
4.Power Source Distortion Factor: <1%
5.Display: Large LCD screen
6.Electrode Gap: Standard 2.5mm(the gas is adjustable)
7. Testing Times: 6 times(1~6 times to choose)
8. Static Placing time: 5min(1~9 mins to choose)
9.Dimension: 670x420x410mm
10.Weight: 42 kg
11. Environment Temperature: 0~40ºC
12. Relative Humidity: ≤85%
13. Working Power: AC220V(1 ± 10%)
14. Power Frequency: 50Hz(1 ± 10%)
15. Power Consumption: <200W
The Instrument Features:
1. The instrument is controlled by large capacity single chip microcontroller, and the work is stable and reliable.
2. The device built-in wide scope of watchdog circuit to eliminate computer crashed phenomenon.
3. The instrument oil cup was cast in a special glass by one time, which eliminated the occurrence of such interference phenomena as oil leakage.
4. The unique high voltage end sampling design of the instrument allows the test value to go directly into the A/D converter, avoid the errors caused in the analog circuit, and making the measurement results more accurate.
5. The instrument has the functions of over-current, overvoltage and short circuit, etc., and has a strong anti-interference ability and electromagnetic compatibility.
6.Portable structure, easy to move, indoor and outdoor use is very convenient.
The Introduction of Host Box and Panel
1. LCD Screen: display date, time, operating parameters, testing results, operating menu prompt and relative information.
2. Functional Buttons: choose to set operating parameters.
3. Printer: print testing results.
4. Change Switches: Choose different boosting rate.
5. Indicator: If the indicator light is on, it means the relative operation is being carried out.
6. Oil Cup Box Lid: open the lid to put in or take out the oil cup, it will begin to test after closing the lid.
7. Temperature and Humidity Sensors: measure the temperature and relative humidity, then switching to digital signals to display.
8. Groundline Pole: reliable groundline connecting pole.
9. Power Socket and Switch: reliable power socket, AC220V 50Hz power line.
10. Press Switch: press it to open or close box lid.
11. High voltage sign: prompt dangerous high voltage triangle sign.
Company Profile
Kiyu Power is a high-tech enterprise professionally engaged in R & D, manufacture and marketing of power testing products, instruments, power industry automation systems for 20 years.We export completed set to Korea, Singapore, Vietnam, India, Ecuador, Paraguay, Pakistan, Philippines, Russia, Italy, Austria, Portugal, Chile such as PD test system, impulse voltage generator, temperature rising test system, transformer comprehensive test system, cable fault detect system and varies of instruments for transformer, circuit breaker, switchgear, lightning arrestor, insulator, cable, battery, SF6 gas and so on.