Customization: | Available |
---|---|
After-sales Service: | Life Time |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated output voltage | 0-1000kV or under |
Output frequency | 30-300Hz |
Resonance voltage waveform | Sine wave, waveform distortion rate ≤1.0% |
Protection | Overvoltage, overcurrent, zero-start and other protective functions |
Work form | Continuous working |
Quality factor | 30-90 |
Frequency adjust sensitivity | 0.1Hz |
Testing accuracy | 1.5% |
Instable degree | <0.05% |
Power source | Single phase 220V or 3 phase 380V ±10% |
Power frequency 50Hz ±5% |
Model | Application(10kV~500kV transformer substation AC voltage withstand equipment, frequency 30~300Hz) | ||||
Frequency Power Source | Resonant Reactor | Excitation transformer | Divider | Application | |
CYBP-BD-50/50/25 | 3kW | 25kV/1A two sets(dry type) | 3kVA(dry type) | 50kV | ≤1000kVA 10kV transformer 10kV switch, busbar, PT, CT ect. 10kV(300mm2) cable≤1.0km |
CYBP-BD-108/108/27 | 5kW | 27kV/1A four sets(dry type) | 5kVA(dry type) | 110kV | ≤31500kVA 35kV transformer 35kV switch, busbar, PT, CT ect. 10kV(300mm2) cable 2km 35kV(300mm2) cable 0.5km |
CYBP-BD-200/200/50 | 10kW | 50kV/1A four sets(dry type) | 10kVA(dry type) | 200kV | ≤50000kVA 110kV transformer 110KV GIS, PT, CT ect.(preventive test) 35kV(300mm2) cable ≤1.0km 10kV(300mm2) cable ≤2.0km |
CYBP-BD-270/270/45 | 15kW | 45kV/1A six sets(dry type) | 15kVA(dry type) | 300kV | ≤50000kVA 110kV transformer 110kV GIS, PT, CT ect. 35kV(300mm2) cable ≤1.2km 10kV(300mm2) cable ≤3.0km |
CYBP-BD-800/400/50 | 30kW | 50kV/2A eight sets(dry type) 100kV/2A four sets(oil immersed) | 30kVA(dry type) 30kA(oil immersed) |
400kV | ≤80000kVA 220kV transformer ≤50000kVA 110kV transformer 110kV/220kV GIS, PT, CT ect. 35kV(300mm2) cable ≤2.0km 110kV(300mm2) cable ≤0.7km |
CYBP-BD-1600/800/200 | 60kW | 200kV/2A four sets(oil immersed) | 60kVA(dry type) | 800kV | ≤80000kVA 220kV transformer ≤50000kVA 110kV transformer 500kV GIS, PT, CT ect. 220kV switch, busbar, PT, CT ect. 110kV(400mm2) cable ≤1.5km 220kV(400mm2) cable ≤1.0km |
Note: Can be customized |