Universal Partial Discharge Measurement and Analysis System

Product Details
Customization: Available
After-sales Service: Lifetime Service
Warranty: 12 Months
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
Cooperated with Fortune 500
This supplier has Cooperated with Fortune 500 companies
Patents Awarded
The supplier had awarded 7 patents, you can check the Audit Report for more information
Quality Assurance
The supplier provides quality assurance
to see all verified strength labels (22)
  • Universal Partial Discharge Measurement and Analysis System
  • Universal Partial Discharge Measurement and Analysis System
  • Universal Partial Discharge Measurement and Analysis System
  • Universal Partial Discharge Measurement and Analysis System
  • Universal Partial Discharge Measurement and Analysis System
  • Universal Partial Discharge Measurement and Analysis System
Find Similar Products

Basic Info.

Model NO.
CYJF-127
Power Interface
6-12VDC (<6W)
Input Interface
Voltage Input Signal, Partial Discharge Input Sign
Frequency Range
5kHz-16MHz
Input Impedance
100Ω/120Ω
Square Wave Output Waveform
Tt≤60ns 100ns <Ts<200ns
Trademark
KIYU POWER
HS Code
9030339000

Product Description

Partial discharge refers to the electric discharge which happens between electric pole and doesn't penetrate electrode, and includes the repeated breakdown and extinguishment under the action of high electric field intensity on account of the weakness in equipment insulation or the defects generated in production process. It is manifested as the breakdown of air in insulation, the partial breakdown of solid or liquid media within small scope, or partial breakdown and discharge resulting from field strength concentration of edges and sharp parts on the surface of metal, etc. Such discharge generates very small energy, so, its transient presence doesn't affect the insulating strength of electrical equipment. If the partial discharge continuously happens to the insulation of electrical equipment at operating voltage, these weak discharge will generate accumulative effect which would gradually deteriorate the insulated dielectric property and expand the local defects, finally resulting in the whole insulation breakdown.

CYJF-127, a type of high-precision, modular and all-digital portable acquisition and analysis system of partial discharge with optical fiber isolation, is composed of a detection impedance, master acquisition unit, optical fiber and fiber optic transceiver, integrates the latest acquisition and processing technology of digital signal, and can provide very high measurement accuracy in harsh environment by virtue of high-resolution digital processing technology and optical fiber isolation technology.


Performance Parameters:

1)Master acquisition unit
a) Interface
Power interface: 6-12VDC (<6W), quick plug with lock;
Optical fiber interface: Support of Gigabit network access;
Input interface: Voltage input signal, partial discharge input signal and square wave output signal (optional).
b)Indicato Light 1XLED
normally on and flicker (power supply indication and communication indication);
15s interval flicker (failure to set up link with the upper computer).
c)Environmental conditions Working 
temperature: -10~60°C;
Storage temperature: -10~70°C;    
Humidity: ≤90% (non-condensation).
d)Partial discharge input
Frequency range: 5KHz-16MHz;
Input impedance: 100Ω/120Ω;
Maximum voltage: 50V peak-to-peak value;
A/D: 14bit,80MS/s;
Dynamic range: about 62dB in total;
Range control: X0.04,X1,X5,X25,X125,X250,X1250; 
Self-noise is less than 50uV.
e)Voltage input
Frequency range: 30Hz-500Hz
Input impedance: 1MΩ;
Maximum voltage: 50Vrms;
A/D: 24bit, 20kHz.
f)Square wave output(optional)
Output frequency: 600Hz;
Output waveform: Tt≤60nS 100nS <Ts<200nS;
Output gear: ±5pC/10pC/20pC/50pC/100pC/200pC/500pC/1000pC.
2)Battery
a)Charge input: 8.4V/5A;
b)Battery output: 7.4V/15Ah;
e)Power adapter: 8.4V/5A (directly used as the host power supply)
Remarks: If battery isn't used for a long time, please store the device on a full charge, and supplement power every 3 months.
3)Communication interface
a)Gigabit Ethernet LAN interface
b)SFP optical fiber interface
c)Receiver USB2.0;
4)Test impedance
a)Rated current: 0.5A;
b)Bandpass range: 17KHz~6MHz ±10%;
c)Low-pressure arm output voltage: ≤50VRMS (please increase the internal low-voltage arm capacitance in case of surpassing the voltage).

Company Profile:
KIYU POWER WUHAN CO., LTD., founded in 2002, is among the earliest brands in the field of electrical power testing in China. With over 22 years of proficiency in the design and manufacture of high-voltage test equipment, the company has created a unique position for itself in the industry.

KIYU POWER provides precise and efficient testing solutions for a broad spectrum of applications, such as power transformers, circuit breakers, GIS, CT/PT, surge arresters, insulators, cables, transformer oil, and insulating materials.

Boasting a cutting-edge facility spanning 26,000 square meters, KIYU POWER guarantees the production of high-quality equipment that conforms to international standards. It also has a professional and efficient technical R & D team that aspires for excellence. They possess in-depth professional knowledge and extensive practical experience, enabling them to offer customized testing solutions for clients. Additionally, it holds numerous technical patents, which earns us recognition and respect in the market.

The products of KIYU POWER have been continuously exported to various countries and regions globally. These successful cases not only bear witness to its technological capabilities but also showcase our contributions to the global electrical power testing industry.

Universal Partial Discharge Measurement and Analysis SystemUniversal Partial Discharge Measurement and Analysis SystemUniversal Partial Discharge Measurement and Analysis SystemUniversal Partial Discharge Measurement and Analysis SystemUniversal Partial Discharge Measurement and Analysis SystemUniversal Partial Discharge Measurement and Analysis System
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier