Customization: | Available |
---|---|
After-sales Service: | Life Time |
Warranty: | 1 Year |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Functions | Insulation resistance testing, voltage testing |
Basic Terms | 23ºC± 5ºC, less than 75%rh |
Rated Voltage(V) | 250, 500, 1000, 2500, 5000, 10kV |
Measuring Voltage(V) | Rated voltage x (1±10%) |
Insulation Resistance Range(GΩ) | 0.01MΩ~2000GΩ |
Insulation Resistance Resolution | 0.01MΩ |
DC Voltage Range | 0~1000V |
DC Voltage Resolution | 0.1V |
AC Voltage Range | 0~750V |
AC Voltage Resolution | 0.1V |
Output short-circuit Current | ≥5mA(5kV) |
Absorption Ratio & Polarization Index | Yes |
Power | 12.6V charge lithium battery |
Background | Adjustable pale screen background light, suitable for gloomy lots using |
Display Model | 4 bytes large LCD display, pale screen background light |
LCD Display Size | 108mm x 65mm |
Instrument Sizes | Length/Width/Height 277.2mm x 227.5mm x 153mm |
USB Interface | USB interface, software monitoring, reserved datas can be upload to computer, save and print |
Communicating Line | USB communicating line 1 set |
Testing Line | HV rod red 3m, hv testing line black 1.5m, green line 1.5m |
Data Reserve | 500 groups, flash display"FULL" means data reservation is full |
Data Inquiry | Data inquiry function: "MR" mark display |
Spilling Display | Over measurement spilling function: "OL" mark display |
Alarm Function | Alarm prompt when the measuring value exceeds setted value |
Power Consumption | Standby: 30mA Max(background turns off) |
Power on background turns on: 42mA Max | |
Measure: 300mA Max(background turns off) | |
Instrument Weight | 2750g(include batter) |
Battery Voltage | When the battery voltage isn't adequate, it shows low energy mark |
Auto Turns off | Auto turns off if there is no operation in 15 mins |
Insulation Resistance | ≥50mΩ(between testing line and housing) |
Withstand Voltage | AC3kV/50Hz 1 min |
Working Temperature and Humidity | -10ºC~+50ºC<85%RH |
Save Temperatur and Humidity | -15ºC~+55ºC<90%RH |
Suitable for Specifications | IEC61010-1, IEC1010-2-31, IEC61557-1, 5, IEC60529(IP54), Pollution level 2, CAT III 300V |